CalcSpec

ABYC E-11 Marine Ampacity Calculator

Enter circuit current, one-way run length, system voltage, conductor temperature rating, location, bundle count, and allowable voltage drop. Returns the minimum AWG sized to ABYC E-11 ampacity tables and the 3% / 10% voltage-drop rule, whichever requires more copper.

Critical-load drop limit
3%
Non-critical drop limit
10%
Engine-room derate
0.58×
Copper K constant
10.75Ω·CM/ft
Continuous load on the conductor
Source to load — calculator doubles for round-trip
Nominal bus voltage
Per ABYC E-11 §11.6.5
Insulation rating (UL Boat Cable / BC-5W2)
Engine room applies E-11 §10.4 derating
Per ABYC Table VII bundle correction
Minimum AWG
Enter values
Voltage-drop AWG
Ampacity AWG
Actual drop at chosen AWG
V
CM required
CM
ABYC reference
Table V / VI / VII
You ran this dockside. Offshore there's no signal.

Marine Toolkit runs this math past cell range

Tip ABYC §11.6.5: critical loads (engine, electronics, blowers, bilge pumps) must be sized for ≤ 3 % drop. Non-critical loads (cabin lights, accessories) tolerate up to 10 %. When in doubt, design to 3 % — voltage drop on a starter motor cable robs cranking torque.

Worked example

30 A panel feed, 25 ft one-way run on a 12 V DC boat, 3 % drop allowed, 75 °C tinned copper, general (non-engine-room) location, single conductor.

1. CM required for voltage drop CM = (K × I × L × 2) / (V × Vd%/100) CM = (10.75 × 30 × 25 × 2) / (12 × 0.03) CM = 16,125 / 0.36 CM = 44,792 2. Smallest AWG with ≥ 44,792 CM #4 AWG = 41,740 CM → too small #2 AWG = 66,360 CM → ✓ Voltage-drop AWG = #2 3. Ampacity check (Table V, 75 °C, general) 30 A load → #10 AWG (40 A rated) is sufficient Ampacity AWG = #10 4. Final = max(#2, #10) Voltage drop dominates. Use #2 AWG copper 5. Actual drop at #2 AWG Vd = (10.75 × 30 × 25 × 2) / 66,360 = 0.243 V Vd% = 0.243 / 12 × 100 = 2.0 % ≈ 0.24 V drop, 1.0 % margin under 3 % limit

Sources

ABYC E-11 AC and DC Electrical Systems on Boats (2023) ABYC Standards & Technical Information Reports USCG 46 CFR §183.340 — uninspected boats IEEE 45.1 Recommended Practice — Shipboard Electrical Calder Boatowner's Mechanical & Electrical Manual (4th ed.)

Common mistakes

Warn Engine-room conductors must use insulation rated ≥ 105 °C (ABYC E-11 Table V) and pass through hot-zone derating. Standard residential THHN is NOT marine-rated — use UL Boat Cable, BC-5W2, or equivalent. Tinned copper is required where corrosion is a risk.

FAQ

Why does ABYC require larger wire than NEC for the same load?

The marine environment derates conductor ampacity per ABYC E-11 §10.4 (ambient compensation). Vibration, salt corrosion, and engine-room heat all reduce safe current capacity, so ABYC tables run more conservative than NEC residential values. A circuit that's fine in a dry wall cavity can overheat in a bilge or behind an engine cover.

Single-conductor vs sheathed cable ampacity?

ABYC Table V (single conductor in free air) gives the highest ampacity. Table VI (2-3 conductor sheathed) is lower, and Table VII (4+ conductors bundled) lower still. Bundling derates because heat from each conductor can't radiate away — the inner cores cook the outer ones. Always count every current-carrying conductor that shares a sheath or wire loom.

12 V vs 24 V system — does wire size differ?

Yes. Halving the voltage doubles the current for the same power (P = V × I). Voltage drop scales linearly with current, so a 12 V boat needs roughly 2× the copper of a 24 V boat at the same load and run length. This is why long bow-thruster runs and inverter feeds often drive a 24 V house bank decision on larger vessels.

Where does the K = 10.75 come from?

It's the resistivity of copper at 75 °C expressed in circular-mil units: ρ ≈ 10.75 Ω·CM/ft. The constant lets you compute voltage drop directly from current, length, and conductor cross-section in CM: Vd = K × I × 2L / CM. Aluminum (rare in marine) uses K ≈ 17.

No bars in the engine room, none past the breakwater

The web page can't load once the boat leaves coverage

Marine Toolkit keeps ABYC E-11 ampacity and tank/scope math on the phone, saves each run, and works in the engine room and offshore. Pay once, own it.

Related

CalcSpec is an estimator for qualified marine technicians, electricians, and surveyors. Results do not replace ABYC certification, USCG inspection, or a licensed marine electrician's judgment. Always verify against the current edition of ABYC E-11 and applicable USCG regulations.