CalcSpec

Refrigerant Charge Calculator

Compare measured versus target superheat and subcooling on TXV and fixed-orifice systems. Includes line-set adjustment for extra tubing. R-410A, R-22, R-32, R-134a.

TXV target subcool
10°F
Fixed target superheat
15°F
R-410A per ft liquid line
0.6oz/ft
In-target band
±3°F
Used for line-set charge per foot
Sets target and primary charging method
At suction line, 6 in from service valve
At liquid line outside condenser
From manufacturer charging chart
From manufacturer charging chart
Length beyond factory allowance
Switches inputs and outputs
Charge status
Charge is OK
TXV, primary = subcooling
Superheat deviation
+5.0°F above target
Subcooling deviation
+2.0°F below target
Line set charge adjustment
+0.0oz
You loaded this on wifi. The attic has none.

HVAC Toolkit runs this math at zero bars

Tip Use subcooling as the primary charging method for TXV systems and superheat for fixed-orifice systems. Always verify airflow and manufacturer charging data before adjusting charge.

Worked example

TXV R-410A system. Measured superheat 15°F, measured subcooling 8°F, target subcooling 10°F, line set 10 ft longer than factory allowance.

1. Primary method = subcooling (TXV) SC deviation = Target − Measured SC dev = 10 − 8 = +2.0°F below target 2. Secondary check = superheat SH dev = Measured − Target SH dev = 15 − 10 = +5.0°F above target 3. Line set adjustment R-410A rate = 0.6 oz/ft Adj = 10 × 0.6 = 6.0 oz to add 4. Field rule SC below target → ADD refrigerant (+6.0 oz line set)

Target superheat & subcooling reference

Metering Refrigerant Target SH (°F) Target SC (°F) Primary method Notes
TXVR-410A1010SubcoolingSH is a secondary check only.
TXVR-221010SubcoolingCompare against the condenser charging chart.
TXVR-321010SubcoolingHigher pressures require accurate instruments.
TXVR-134a1010SubcoolingCommon on medium-temp refrigeration equipment.
FixedR-410A158SuperheatSC is a secondary check only.
FixedR-22158SuperheatIndoor + outdoor conditions affect target SH.
FixedR-32158SuperheatConfirm compatible charging procedures.
FixedR-134a158SuperheatEvaporator feeding is the main indicator.

Common mistakes

Warn Charging decisions must be based on stable operating conditions and the manufacturer's charging chart for the specific equipment. EPA Section 608 certification is required to handle refrigerant in the United States.

FAQ

How do I know if my AC is low on refrigerant?

Low charge often shows up as high superheat on a fixed-orifice system or low subcooling on a TXV system. You may also see reduced cooling capacity, longer run times, low suction pressure, or a starved evaporator. Always verify airflow, coil cleanliness, and metering device operation before concluding the system is undercharged.

What is the difference between superheat and subcooling charging methods?

Superheat tells you how far refrigerant vapor has been heated above saturation after the evaporator — useful on fixed-orifice systems where charge directly affects evaporator feeding. Subcooling tells you how far liquid has been cooled below condensing saturation — useful on TXV systems where the valve regulates evaporator superheat and condenser liquid inventory becomes the better charging indicator.

How much refrigerant should I add per foot of extra line set?

Field estimate for a 3/8 in liquid line: about 0.6 oz/ft R-410A, 0.6 oz/ft R-454B, 0.3 oz/ft R-22, 0.6 oz/ft R-32, 0.4 oz/ft R-134a. Manufacturer line-set tables are more reliable because standard factory-charge length, tubing size, and application details can change the value.

Can I mix refrigerants when topping off charge?

No. Mixing refrigerants creates an unknown blend with different pressure-temperature behavior and oil compatibility. Recover the charge properly and recharge with the exact refrigerant listed on the nameplate.

What causes refrigerant leaks?

Vibration wear, poor brazing, flare leaks, damaged Schrader cores, rubbed copper lines, coil corrosion, and mechanical damage during installation or service. Refrigerant is not consumed in normal operation — find and repair the leak instead of repeatedly topping off.

Sources

ASHRAE Handbook — Refrigeration (2022) EPA Section 608 refrigerant-handling rules AHRI Standard 700 purity spec Chemours Opteon line-set charge tables
No LTE on the roof, none in the crawlspace

The web page won't load where you charge the unit

HVAC Toolkit keeps R-410A/R-454B PT curves on the phone, logs each check, and exports the run for the ticket. No signal, no login. Pay once.

Related

CalcSpec is an estimator for qualified technicians. Results do not replace manufacturer charging charts, AHRI-certified gauges, or the judgment of a licensed HVAC contractor. Always follow EPA Section 608 refrigerant-handling requirements.