CalcSpec

Refrigerant Superheat Calculator

Enter suction pressure and suction line temperature. Returns superheat, saturation temperature, and whether you're in the target window for fixed-orifice or TXV systems. PT data for R-410A, R-22, R-32, R-454B.

Fixed orifice target
8–20°F
TXV / EEV target
8–12°F
Floodback risk below
5°F
Starvation risk above
25°F
PT data from ASHRAE Handbook — Fundamentals (2021) & manufacturer literature
Sets the target superheat window
Gauge pressure at the service port
Clamp-on thermocouple, 6 in from service valve
Superheat
°F
Enter values
Saturation temp (SST)
°F
Target range
8–12°F
Suction pressure
psig
Metric
°C @ kPa
You loaded this on wifi. The attic has none.

HVAC Toolkit runs this math at zero bars

Tip Insulate the thermocouple to the line and wait 60 seconds before reading. Ambient air on the probe tip adds 2–4°F of apparent superheat on a 95°F day.

Worked example

R-410A system, TXV metering. Gauge reads 130 psig at the suction service port; clamp-on thermocouple reads 52°F on the line 6 inches from the valve.

1. Saturation temp at 130 psig R-410A SST = 40.3°F (from PT curve) 2. Superheat SH = T_line − SST SH = 52.0 − 40.3 SH = 11.7°F 3. Evaluate against target TXV target: 8–12°F → In target window. No charge adjustment.

PT reference — R-410A (condensed)

Pressure (psig)Sat. temp (°F)Pressure (kPa)Sat. temp (°C)

Values interpolated for the full range by the calculator above. Full bubble + dew data in the refrigerant PT charts.

Common mistakes

Warn Below 5°F superheat, assume liquid floodback risk. Recover charge, check TXV sensing bulb contact and insulation, verify indoor airflow (≥350 CFM/ton). Do not leave the system running in this state.

FAQ

What is a normal superheat value?

TXV or EEV systems target 8–12°F at the evaporator outlet. Fixed-orifice systems target 8–20°F at the compressor, and the exact number depends on indoor wet-bulb and outdoor dry-bulb — consult the manufacturer's charging chart on the unit nameplate.

Do I measure at the evaporator or the compressor?

TXV/EEV superheat ("evaporator superheat") is measured at the evaporator outlet, before the suction line warms in the attic or service chase. Total superheat ("compressor superheat") is measured at the compressor inlet and includes suction-line heat gain — always higher than evaporator superheat.

Why do R-410A and R-454B read different superheats at the same pressure?

They have different saturation curves. R-454B runs about 1–2°F lower saturation temp than R-410A at the same pressure in the A/C range, so the same line temp yields slightly higher superheat on R-454B. Use the PT data for the actual refrigerant in the system.

Does elevation affect the reading?

The saturation relationship is absolute-pressure-based, but service gauges read gauge pressure. At 5,000 ft (atmospheric ≈ 12.2 psia), a gauge reading the same psig corresponds to a lower absolute pressure than at sea level — a 2.5 psi difference shifts R-410A SST by about 1°F. Manufacturer charging charts assume sea level unless noted.

Sources

ASHRAE Handbook — Fundamentals, Ch. 30 (2021) Chemours Opteon PT relationships Honeywell Solstice / Genetron tech sheets AHRI Standard 700 purity spec
No LTE on the roof, none in the crawlspace

The web page won't load where you charge the unit

HVAC Toolkit keeps R-410A/R-454B PT curves on the phone, logs each check, and exports the run for the ticket. No signal, no login. Pay once.

Related

CalcSpec is an estimator for qualified technicians. Results do not replace manufacturer charging charts, AHRI-certified gauges, or the judgment of a licensed HVAC contractor. Always follow EPA Section 608 refrigerant-handling requirements.